Ultra 5

 Non-Contacting Level and Pump Control and Flow Measurement

  • 5 control relays
  • Measurement range 125 mm to 40 m (5 in to 131 ft)
  • Optional 4-20mA input
  • Pre-programmed tank shapes
  • Power run-on
  • Pump Exercising
  • Start point variation | Storm Control | Aeration control | Flush valve Control | Differential level control
  • Description
  • Reviews (0)
  • Specifications
  • Brochure
  • User’s Guide

Product Description

Ultra 5 provides flexible and reliable non-contacting ultrasonic level and volume measurement, advanced pump control, and measures open channel flow, with different mounting options available to suit the application. The Ultra 5 features the Ultra Wizard, an onboard, menu-driven software tool that allows the user to quickly and simply set up an Ultra 5 unit for a specific application.

Using a ‘Quick Setup’ menu, specific to the application, it allows parameters such as empty and full distances and alarm/control relay settings to be entered. The Ultra Datalogger provides all wall mounted Ultra Controllers with data logging functionality, recording a wealth of information onto the supplied 8 GB Micro SD card, enabling the user to log data for the lifetime of the product.

Reviews

There are no reviews yet.


Be the first to review “Ultra 5”

General Specifications
Spec: Description:
Transducer Cable Extensions 2-core screened
Maximum Separation 1,000 m (3,280 ft)
Operating Temperature (Electronics) -20 °C to +50 °C (-4 °F to +120 °F)
Accuracy and Repeatability 0.25% of the measured range or 6 mm (0.24 in) (whichever is greater)
Resolution 0.1% of the measured range or 2 mm (0.079 in) (whichever is greater)
Min. and Max. Range 0 m - 40 m (0 ft - 131 ft). Dependent on the sensor used. Ability to measure 50 m (164 ft) with dB50 when modified.
Analog Output Isolated (floating) output (to 150 V) of 4-20mA or 0-20mA into 500 Ω (user programmable and adjustable) 0.1% resolution
Digital Output Full Duplex RS232
Volt-free Contacts, Number and Rating 5 form “C” (SPDT) rated at 5 A at 240 V AC
Display 6 digits plus 12 character text, plus bar graph with direction indicators, remote communicator identifier, and program/run/test mode indicators
Options
Option: Description:
Mounting Options Wall Mount, Fascia Mount, Rack Mount, Panel Mount
Data Logger SD Card data logger
Communications RS485 Modbus & Data logging option
Profibus & Data logging Option V1

Approvals:

  • CE Approval
  • Flammable Atmosphere Approval
  • Up to IP65

ultra 5 Brochure

Ultra 5 Data Sheet

Ultra 5 User's Guide

Open chat